EDR-3000 IM02602003E
Direct Commands of the Breaker Wear Module
Parameter Description Setting range Default Menu path
Res TripCmdCr Resetting of the Counter: total number of trip commands Inactive,
Active
Inactive [Operation
/Reset]
Res Isum trip Reset summation of the tripping currents Inactive,
Active
Inactive [Operation
/Reset]
Res Isum Intr per
hour
Sum per hour of interrupting currents. Inactive,
Active
Inactive [Operation
/Reset]
Res Bkr OPEN
capacity
Resetting of the CB OPEN capacity. 100% means, that
the breaker is to be maintenanced.
Inactive,
Active
Inactive [Operation
/Reset]
Trigger signals for Sync-check
NOTICE: The “Syn-check” function is not available on EMR-XXXX devices.
The following signals can be used to indicate synchronism
Name Description
-.- No assignment
DI-4P X1.DI 1 Signal: Digital Input
DI-4P X1.DI 2 Signal: Digital Input
DI-4P X1.DI 3 Signal: Digital Input
DI-4P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 1 Signal: Digital Input
DI-8P X1.DI 2 Signal: Digital Input
DI-8P X1.DI 3 Signal: Digital Input
DI-8P X1.DI 4 Signal: Digital Input
DI-8P X1.DI 5 Signal: Digital Input
www.eaton.com 391