EDR-3000 IM02602003E
Global Protection Parameters of the Switch Onto Fault Module
Parameter Description Setting range Default Menu path
Mode Mode Bkr State,
I<,
Bkr State And I<,
Bkr manual CLOSE,
Ext SOTF
Bkr manual
CLOSE
[Protection Para
/Global Prot Para
/SOTF]
ExBlo1 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/SOTF]
ExBlo2 External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/SOTF]
Rvs Blo Reverse Blocking, if Reverse Blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.- [Protection Para
/Global Prot Para
/SOTF]
Ext SOTF External Switch Onto Fault
Only available if: Mode = Ext SOTF
1..n, DI-LogicList -.- [Protection Para
/Global Prot Para
/SOTF]
www.eaton.com 496