EDR-3000 IM02602003E
Setting Group Parameters of the Switch Onto Fault Module
Parameter Description Setting range Default Menu path
Function Permanent activation or deactivation of module/element. Inactive,
Active
Inactive [Protection Para
/<1..4>
/SOTF]
ExBlo Fc Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/SOTF]
Rvs Blo Fc Activate (allow) or inactivate (disallow) reverse blocking
of the module/element. This parameter is only effective if
a signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/element are blocked that are parameterized
"Rvs Blo Fc = active".
Inactive,
Active
Inactive [Protection Para
/<1..4>
/SOTF]
I< The breaker is in the OPEN Position, if the measured
current is less than this parameter.
0.01 - 1.00In 0.01In [Protection Para
/<1..4>
/SOTF]
t-enable While this timer is running, and while the module is not
blocked, the Switch Onto Fault Module is effective (SOTF
is armed).
0.10 - 10.00s 2s [Protection Para
/<1..4>
/SOTF]
www.eaton.com 497