EDR-3000 IM02602003E
Application Options of the Fault Simulator**:
Stop Options
Cold Simulation (Option 1) Hot Simulation (Option 2)
Do not stop
Run complete:
Pre Failure, Failure, Post Failure.
How To?: Call up [Service/Test Mode (Prot
inhibit)/WARNING! Cont?/Sine wave
gen/Process]
Ex Force Post = no assignment and
Press/Call up Start Simulation.
Simulation without tripping the
breaker:
Blocking protective Trips to the
Breaker. That means verifying if
the protective device generates a
trip without energizing the trip coil
of the breaker (similar to disarm
the output relay).
How To?:
Call up [Service/Test Mode (Prot
inhibit)/WARNING! Cont?/Sine
wave gen/Process]
Trip Cmd Mode = No Trip
Simulation is authorized to trip
the breaker:
How To?:
Call up [Service/Test Mode (Prot
inhibit)/WARNING! Cont?/Sine
wave gen/Process]
Trip Cmd Mode = Trip
Stop by external signal
Force Post: As soon as this signal becomes
true, the Fault Simulation will be forced to
switch into the Post Failure mode.
How To?: Call up [Service/Test Mode (Prot
inhibit)/WARNING! Cont?/Sine wave
gen/Process]
Ex Force Post = Assigned Signal
Manual stop
As soon as this signal becomes true, the
Fault Simulation will be terminated and the
device changes back to normal operation.
How To?: Call up [Service/Test Mode (Prot
inhibit)/WARNING! Cont?/Sine wave
gen/Process]
Press/Call up Stop Simulation.
**Please note: Due to internal dependencies, the frequency of the simulation module is 0.16% greater than the rated one.
www.eaton.com 630