EDR-3000 IM02602003E
Parameter Description Setting range Default Menu path
IB Fund. Current Fundamental Magnitude in Pre State: Phase B 0.00 - 40.00In 0.0In [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/CT]
IC Fund. Current Fundamental Magnitude in Pre State: Phase C 0.00 - 40.00In 0.0In [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/CT]
IX meas Fund. Current Fundamental Magnitude in Pre State: IX 0.00 - 25.00In 0.0In [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/CT]
Angle IA Fund. Start Position respectively Start Angle of the Current
Phasor during Pre Phase:Phase A
-360 - 360° 0° [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/CT]
www.eaton.com 633