EDR-3000 IM02602003E
Parameter Description Setting range Default Menu path
Ex Start Simulation External Start of Fault Simulation (Using the test
parameters)
1..n, Assignment
List
-.- [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Process]
ExBlo External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
Bkr.Pos CLOSE [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Process]
Ex ForcePost Force Post state. Abort simulation. 1..n, Assignment
List
-.- [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Process]
Current Parameter of the Failure Simulator
Parameter Description Setting range Default Menu path
IA Fund. Current Fundamental Magnitude in Pre State: Phase A 0.00 - 40.00In 0.0In [Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PreFault
/CT]
www.eaton.com 632