77
BACnet MS/TPOn-Board Communication
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Object instance summary
Binary Value Object Instance Summary
The following table summarizes the Binary Value Objects supported.
Table 92. Binary value object instance summary
Instance
ID
Object name (related
To drive parameter) Description Inactive/Active text
Preset value
access
BV0 Ready State Indicates whether the drive is ready or not Not Ready/Ready R
BV1 Run/Stop State Indicates whether the drive is running or stopped Stop/Run R
BV2 Fwd/Rev State Indicates the rotation direction of motor Fwd/Rev R
BV3 Fault State Indicates if a fault is active OK/Fault R
BV4 Warning State Indicates if a warning is active OK/Warning R
BV5 At Setpoint Ref. Frequency reached False/True R
BV6 At Zero Speed Motor Running at zero speed False/True R
BV7 Motor Ctrl source Command to change active source for controlling motor LocalMotorCtrl / FBMotorCtrl C
BV8 Speed Reference Source Command to change source of motor speed reference LocalSpeedRef / FBSpeedRef C
BV9 Run/Stop CMD Command to start drive Stop/Run C
BV10 Fwd/Rev CMD Command to change rotational direction Fwd/Rev C
BV11 Reset Fault Command to reset active Fault from drive 0/Reset C
BV12 Digital Input 1 Digital Input 1 OFF/ON R
BV13 Digital Input 2 Digital Input 2 OFF/ON R
BV14 Digital Input 3 Digital Input 3 OFF/ON R
BV15 Digital Input 4 Digital Input 4 OFF/ON R
BV16 Digital Input 5 Digital Input 5 OFF/ON R
BV17 Digital Input 6 Digital Input 6 OFF/ON R
BV18 Digital Input 7 Digital Input 7 OFF/ON R
BV19 Digital Input 8 Digital Input 8 OFF/ON R
BV20 Digital Output 1 Digital Output 1 OFF/ON R
BV21 Digital Output 2 Relay 1 Output OFF/ON R
BV22 Digital Output 3 Relay 2 Output OFF/ON R
BV23 Digital Output 4 Relay 3 Output OFF/ON R
BV24 Stop By Coast Indicates if drive stop by coast ON/OFF C
BV25 Stop By Ramp Indicates if drive stop by Ramp OFF/ON C
BV26 Belt Broken Indicates If belt is broken OFF/ON R
BV27 Drive Fan Failure Indicates if Drive Fan failed OFF/ON R
BV28 Force Bypass Command to take Drive in Bypass Mode OFF/ON C
BV29 Fire Mode Enable Fire Mode OFF/ON C
BV30 DIN 1 Fieldbus Digital Input OFF/ON C
BV31 DIN 2 Fieldbus Digital Input OFF/ON C
BV32 DIN 3 Fieldbus Digital Input OFF/ON C
BV33 DIN 4 Fieldbus Digital Input OFF/ON C
ote: N For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable.