131
Hardware specifi cation
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Assembly instance 73
Table 160. Instance 73 (Input) length = 6 bytes
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 AtReference RefFromNet CtrlFromNet Ready Running2 Running1 Warning Faulted
1 Drive State
2 Speed actual (Low Byte), rpm
3 Speed actual (High Byte), rpm
4 Torque actual (Low Byte), Nm
5 Torque actual (High Byte), Nm
Refer “State transition diagram,” provided under “Control Supervisor Object” and “Drive State
table specified at end of “Input Instances” section.
Drive State
0x00 DN_NON_EXISTANT
0x01 DN_STARTUP
0x02 DN_NOT_READY
0x03 DN_READY
0x04 DN_ENABLED
0x05 DN_STOPPING
0x06 DN_FAULT_STOP
0x07 DN_FAULTED
Assembly instance 75
Table 161. Instance 75 (Input) length = 6 bytes
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 AtReference RefFromNet CtrlFromNet Ready Running2 Running1 Warning Faulted
1 Drive State
2 Speed actual (Low Byte), rpm
3 Speed actual (High Byte), rpm
4 Process actual (Low Byte), Nm
5 Process actual (High Byte), Nm
Refer “State transition diagram,” provided under “Control Supervisor Object” and
“Drive State” table specified at end of “Input Instances” section.
Drive State
0x00 DN_NON_EXISTANT
0x01 DN_STARTUP
0x02 DN_NOT_READY
0x03 DN_READY
0x04 DN_ENABLED
0x05 DN_STOPPING
0x06 DN_FAULT_STOP
0x07 DN_FAULTED
Process actual value is same as process reference. This value will be a 0 to 10000 (100.00%)
for use with Analog outputs writing, 0 = 0 or 4 mA and 10000 being 20 mA.