Figure 13. Module and network status
Module status indications
Represents the state of the drive.
Table 32. Module status LED description
Indicator state Summary Meaning
Steady Off No power No power is supplied to the device.
Steady Green Device operational Device is operating correctly.
Flashing Green
Standby Device has not been configured.
Flashing Red
Minor fault Device has detected a recoverable minor fault.
Note. An incorrect or inconsistent configuration would be considered a minor fault.
Also check that on clearing the fault, it turns off.
Steady Red Major fault Device has detected a non-recoverable major fault.
Flashing Green/Red
Self-test Device is performing its power up testing.
Flash rate is 1 flash per second.
Network status indications
Represents the state of the Ethernet port network interface.
Table 33. Network status LED description
Indicator state Summary Meaning
Steady Off Not powered, no IP address Device is powered off, or is powered on but with no IP address configured (Interface
Configuration attribute of the TCP/IP Interface Object).
Flashing Green
No connections An IP address is configured, but no CIP connections are established, and an Exclusive Owner
connection has not timed out.
Steady Green Connected At least one CIP connection (any transport class) is established, and an
Exclusive Owner connection has not timed out.
Flashing Red
Connection timeout Device is powered on and an exclusive Owner connection has timed out. It returns to steady
green only when all timed out Exclusive Owner connections are established.
Steady Red Major fault Device has detected a non-recoverable major fault.
Flashing Green/Red
Self-test Device is performing its power up testing.
Flash rate is 1 flash per second.