33
EtherNet/IP On-Board Communications
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Figure 21. Module and network status
Module Status
Network Status
Module status indications
Represents the state of the drive.
Table 58. Module status LED description
Indicator state Summary Meaning
Steady off No power No power is supplied to the PowerXL.
Steady green Device operational Drive is operating correctly.
Flashing green
Standby Drive has not been configured.
Flashing red
Minor fault Drive has detected a recoverable minor fault.
Note. An incorrect or inconsistent configuration would be considered a minor fault.
Also check that on clearing the fault, it turns off.
Steady red Major fault Drive has detected a non-recoverable major fault.
Flashing green/red Self-test Drive is performing its power on self test.
Network status indications
Represents the state of the Ethernet port network interface.
Table 59. Network status LED description
Indicator State Summary Meaning
Steady off Not powered, no IP address Drive is powered off, or is powered on but with no IP address configured (Interface
Configuration attribute of the TCP/IP Interface Object).
Flashing green
No connections An IP address is configured, but no CIP connections are established, and an Exclusive Owner
connection has not timed out.
Steady green Connected At least one CIP connection (any transport class) is established, and an
Exclusive Owner connection has not timed out.
Flashing red
Connection timeout Drive is powered on and an exclusive Owner connection has timed out. It returns to steady
green only when all timed out Exclusive Owner connections are established.
Steady red Duplicate IP address Drive has detected a Duplicate IP.
Flashing green/red Self-test Drive is performing its power on self test.
Flash rate is 1 flash per second.