133
Hardware specifi cation
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Assembly instance 117
Table 163. Instance 117 (Input). EIP drive status length = 34 bytes
ByteBit 7Bit 6Bit 5Bit 4Bit 3Bit 2Bit 1Bit 0
0 CtrlFromNet At Zero Speed At Reference Alarm/Warning Faulted Direction Running Ready
1NA
2 % Speed Actual (Low Byte)
3 % Speed Actual (High Byte)
4 RPM Speed Actual (Low Byte)
5 RPM Speed Actual (High Byte)
6Reserved
7Reserved
8Reserved
9Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
16 Reserved
17 Reserved
18 ProcessDataOut1 (LowByte)
19 ProcessDataOut1 (HighByte)
20 ProcessDataOut2 (LowByte)
21 ProcessDataOut2 (HighByte)
22 ProcessDataOut3 (LowByte)
23 ProcessDataOut3 (HighByte)
24 ProcessDataOut4 (LowByte)
25 ProcessDataOut4 (HighByte)
26 ProcessDataOut5 (LowByte)
27 ProcessDataOut5 (HighByte)
28 ProcessDataOut6 (LowByte)
29 ProcessDataOut6 (HighByte)
30 ProcessDataOut7 (LowByte)
31 ProcessDataOut7 (HighByte)
32 ProcessDataOut8 (LowByte)
33 ProcessDataOut8 (HighByte)
This is the actual value from the frequency converter. The value is between 0 and 10000.
In the application, the value is scaled in percentage of frequency area between set minimum and maximum
frequency. (0 = 0.00%–0000 = 100.00%).
The RPM Speed Actual is the actual speed of the motor. The unit is RPM.
ote: N See Appendix B for Process Data Value defaults.