EasyManua.ls Logo

Eaton PowerXL Series - Profibus-Dp External Communication Cards; PROFIBUS Specifications; Table 97. PROFIBUS Technical Data; Table 98. Line Length

Eaton PowerXL Series
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
80
PROFIBUS-DP External Communication Cards
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
PROFIBUS-DP External Communication Cards
PowerXL Series can be connected to the PROFIBUS
®
DP
using an optional PROFIBUS communication card. PowerXL
Series drive can be controlled, monitored and programmed
from the Host system. The devices are connected in a bus
structure. There is a max of 32 stations (master or slave) can
be connected to one segment bus. The bus is terminated
at beginning and end of each segment. To ensure error-free
operation, both bus terminations must always be powered,
ifmore than 32 stations are used, repeaters are required.
PROFIBUS specifications
Table 96. PROFIBUS technical data
Items Value
Terminal DB9 connector (Female) or 5.00 mm connector (male)
Data transfer method RS-485 half-duplex
Cable Twisted pair (1 pair and shield)
Isolation 500 Vdc
Protocol PROFIBUS-DP-V1
DOIO type ST1 Telegram
Baud rate 9.6K~12M
Addresses 2~125
Environment
Ambient operating
temperature
–1C to +55°C
Storing temperature 4C to +6C
Humidity <95%, no condensation allowed
Altitude Max. 1000m
Vibration 0.5G at 9–200 Hz
Safety Fulfills EN 50178 standard
Table 97. Line length
Baud rate (kbit/s) 9.6 19.2 93.75 187.5 500 1500 3000–12000
Length line A [m] 1200 1200 1200 1000 400 200 100
Length line B [m] 1200 1200 1200 600 200
ote: N Line length depends on different transmission speeds.