172
Commissioning
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
BACnet/IP parameters
Table 199. BACnet/IP parameter descriptions
ID Name Description
P12.4.1.9
Enable BACnet/IP This parameter enables BACnet IP communications. When this parameter is enabled, other parameters in
menu becomes visible, else they are hidden.
P12.4.3.1
BACnet/IP UDP port number The UDP port for the BACnet IP communication.
P12.4.3.2
BACnet/IP Foreign Device The foreign device feature is used when the device is located in a different network than the BBMD.
A normal router does not send broadcast messages between different networks. The ‘Foreign device’
feature solves this problem by establishing a connection to the BBMD with unicast messages. All
broadcast messages are forwarded to a BBMD device that takes care of receiving and transmitting
broadcast messages in both directions for all foreign devices.
P12.4.3.3
BACnet/IP BBMD IP The IP address of the BACnet IP Broadcast Management Device.
P12.4.3.4
BACnet/IP BBMD Port The BBMD Port number.
P12.4.3.5
BACnet/IP Registration Interval The registration interval to keep a live connection to the BBMD. Unit is seconds.
P12.4.3.6
BACnet/IP Comm Timeout Defines the number of seconds after a timeout is indicated after a communication break or disconnected
EtherNet link. Value 0 disables communication link supervision.
P12.4.3.7
BACnet/IP Protocol Status Fieldbus Protocol Status tells the status of the protocol.
P12.4.3.8
BACnet/IP Fault Behavior Defines when Fieldbus fault to be raise if fault condition is detected.
P12.4.3.9
BACnet/IP Instance Number The Device Object’s Instance number is used in conjunction with the MAC address to assign the devices
on the network. The instance number can have up to 127 nodes on it before a different instance number is
required.
BACnet overview
BACnet technical data
Protocol Implementation Conformance Statement (PICS)
Controller Profile
B—ASC
Segmentation Capability
Not supported
Data Link Layer and Routing Options
10/100 MBit/s, Autosensing
Character Sets Supported
UTF8
BIBBS Supported
Data Sharing
ReadProperty
B
WriteProperty
B
Device Management
Dynamic Device Binding
B
Dynamic Object Binding
B
DeviceCommunicationControl
B
ReinitializeDevice
B
Alarms and Events: Not supported
Schedules: Not supported
Trends: Not supported
Network Management: Not supported