PROFIBUS-DP External Communication Cards
POWERXL SERIES VFD   MN040010EN—June 2018   www.eaton.com
General state machine
State diagrams are defined for the operating modes. In the 
PROFIdrive control profile, the controls bits 0 to 3 perform 
the basic start-up / power down functions whereas the 
control bits 4 to 15 perform application-oriented control.
Figure 43.  General state diagram
Notes:  STW1 bit x, y = These control word bits shall be set by the control.
  ZSW1 bit x, y = These status word bits indicate the actual state.
Standstill detected is an internal result of a stop operation. 
 a  Abbr.: “p.e.” = “Pulses enabled” optional.
 b  The internal condition “fault with ramp stop” also activates this transition.
Information on the general state diagram
 •
The green blocks represent states, the arrows represent 
transitions
 •
From several states, several transitions are possible
 •
The more points that a transition has, the higher is its 
priority. A transition without points has the lowest priority
 •
The PROFIBUS interfaces between this controller and the 
DO has the control priority (PNO 928)
 •
ZSW1 Bit 9 is set by the DO
 •
STW1 Bit 10 is set by the controller
 •
The bits defined for positioning mode are only relevant, if 
the drive is in the state “S4” operation
 •
All stop-reactions caused by faults (Fault with Ramp 
stop, Fault with Quick stop, Fault with Coast stop) for the 
general state machine to switch to state S1 (Switching on 
Inhibited) or S2 (Ready For switching)