POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Fixed status word
Table 139. Fixed status word
Bit Name
0Ready
1RUN
2Counterclockwise
3Faulted
4Warning
5 Ref. Frequency reached
6Bypass
7Run enable
8Not in use
9Not in use
10 Not in use
11 Not in use
12 Not in use
13 Not in use
14 Not in use
15 Not in use
Bit
Description
Value = 0 Value = 1
0Not Ready Ready
1STOP RUN
2 Clockwise Counterclockwise
3— Faulted
4— Warning
5 Ref. frequency not reached Ref. Frequency reached
6 Motor is running in bypass
7 Disable motor run Enable motor run
8–15 Not in use Not in use
Actual speed percentage
The Actual Speed Percentage indicates the actual speed
value of the motor. This value will be read as a 0 to
10000value, which indicates 0 to 100.00% speed actual.
FB process data out
The Process Data Out value is assigned by the Fieldbus
Parameter group in the application parameters. These
8values can be set to any available Modbus ID value listed.
See Appendix B to reference the default Process Data Out
values assigned.