BACnet MS/TPOn-Board Communication
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Figure 36. PowerXL DH1 BACnet MSTP parameter navigation
1. First ensure that the right fieldbus protocol is selected.
Navigate:
Main Menu
Parameter Communication RS485 Bus RS-485 Comm Set Edit
(Choose Protocol asBACnet MS/TP)
BACnet MS/TP Parameters and monitoring values
Table 90. BACnet MS/TP Parameter Table
DG1
code
DH1
code Parameter Min. Max. Unit Default ID Note
P20.3.1.1 P12.3.1.1 RS4 85 Comm Set 0 586
0 = Modbus RTU
1 = BACnet MS/TP
P20.3.3.1 P12.3.3.1 BACnet Baud Rate 2 594
0 = 9600
1 = 19200
2 = 38400
3 = 768000
4 = 115200
P20.3.3.2 P12.3.3.2 MAC Address 0 127 1 595
P20.3.3.3 P12.3.3.3 Instance Number 0 4194302 varies 596
P20.3.3.4 P12.3.3.4 Comm Timeout BACnet ms 10000 598
P20.3.3.5 P12.3.3.5 Protocol Status 0 599
0 = Stopped
1 = Operational
2 = Faulted
P20.3.3.6 P12.3.3.6 Fault Code 0 600
0 = None
1 = Sole Master
P20.3.3.7 P12.3.3.7
Modbus RTU/BACNet
Fault Response01 02516
0 = In Fieldbus Control
1 = in all Control
P12.3.3.8 Max Master 0 127 127 1537