143
Hardware specifi cation
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Table 176. Control supervisor object, class 0x29
Object descriptions
Class attributes
ID Description NV Data type Access rule Default Range
01h Revision NV UINT Get 1 —
02h Max instance NV UINT Get 1 —
03h Number of instances NV UINT Get 1 —
Class services
ID Service Requirements
0Eh Get attribute single
Instance attribute
ID Description NV Data type Access rule
03h Run1 V BOOL Get/Set 0 0–1
04h Run2 V BOOL Get/Set 0 0–1
05h NetCtrl V BOOL Get/Set 0 0–1
06h State V USINT Get 0 0–7
07h Running1 V BOOL Get 0 0–1
08h Running2 V BOOL Get 0 0–1
09h Ready V BOOL Get 0 0–1
0Ah Faulted V BOOL Get 0 0–1
0Bh Warning V BOOL Get 0 0–1
0Ch FaultRst V BOOL Get/Set 0 0–1
0Fh CtrlFromNet V BOOL Get 0 0–1
0Dh Active fault code
V UINT Get 0 0–65535
6Ch Comm idle action value
NV USINT Get/Set 2 0–2
6Dh Comm timeout NV UINT Get /Set 10 sec 0-60 sec
Instance services
ID Service
0Eh Get_attribute_single
10h Set_attribute_single
05h Reset Type 0
See Appendix C for Active list of fault codes.
Modification of Attribute 0x6C of Supervisory.
•
Default value for this attribute to be Fault on idle Communication mode
•
This attribute to have 3 values as
• 0 = No Action (Hold Last State) in Idle Communication mode
• 1 = Stop Motor in Idle Communication mode
• 2 = Fault Motor in Idle Communication mode