EtherNet/IP On-Board Communications
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Connections and wiring
The EtherNet/IP board supports 10/100 Mb speeds in both
full and half-duplex modes. The boards must be connected
to the Ethernet network with a shielded CAT-5e cable.
Acrossover cable (at least CAT-5e cable with STP, shielded
twisted pair) may be needed if you want to connect the
EtherNet/IP board directly to the master appliance.
Use only industrial standard components in the network
and avoid complex structures to minimize the length of
response time and the amount of incorrect dispatches. It is
often a good practice to use a subnet that is different from
other devices not related to the drive control.
Figure 24. CAT-5e cable
Table 60. EtherNet/IP network settings
DG1
code Parameter Min. Max. Unit Default ID Note
P20.4.1 IP Address Mode 1 1500 0 = Static IP
1 = DHCP with AutoIP
P20.4.2 Active IP Address 1507
P20.4.3 Active Subnet Mask 1509
P20.4.4 Active Default Gateway 1511
P20.4.5 MAC Address 1513
P20.4.6 Static IP Address 192.168.1.254 1501
P20.4.7 Static Subnet Mask 255.255.255.0 1503
P20.4.8 Static Default Gateway 192.168.1.1 1505
P20.4.9 EtherNet/IP Protocol Status 0 608 0 = Off
1 = Operational
2 = Faulted
P20.4.10 EIP Fault Response 0 1 0 2518 0 = In Fieldbus Control
1 = in all Control