Object instance summary
Binary Value Object Instance Summary
The following table summarizes the Binary Value Objects supported.
Table 201. Binary value object instance summary
Instance
ID
Object name (related
to drive parameter) Description
Inactive/
active text
Preset
value access
BV0
Ready State Indicates whether the drive is ready or not Not Ready/Ready R
BV1
Run/Stop State Indicates whether the drive is running or stopped Stop/Run R
BV2
Fwd/Rev State Indicates the rotation direction of motor Fwd/Rev R
BV3
Fault State Indicates if a fault is active OK/Fault R
BV4
Warning State Indicates if a warning is active OK/Warning R
BV5
At Setpoint Ref. Frequency reached False/True R
BV6
At Zero Speed Motor Running at zero speed False/True R
BV7
Motor Ctrl source Command to change active source for controlling motor LocalMotorCtrl / FBMotorCtrl C
BV8
Speed Reference Source Command to change source of motor speed reference LocalSpeedRef / FBSpeedRef C
BV9
Run/Stop CMD Command to start drive Stop/Run C
BV10
Fwd/Rev CMD Command to change rotational direction Fwd/Rev C
BV11
Reset Fault Command to reset active Fault from drive 0/Reset C
BV12
Digital Input 1 Digital Input 1 OFF/ON R
BV13
Digital Input 2 Digital Input 2 OFF/ON R
BV14
Digital Input 3 Digital Input 3 OFF/ON R
BV15
Digital Input 4 Digital Input 4 OFF/ON R
BV16
Digital Input 5 Digital Input 5 OFF/ON R
BV17
Digital Input 6 Digital Input 6 OFF/ON R
BV18
Digital Input 7 Digital Input 7 OFF/ON R
BV19
Digital Input 8 Digital Input 8 OFF/ON R
BV20
Digital Output 1 Digital Output 1 OFF/ON R
BV21
Digital Output 2 Relay 1 Output OFF/ON R
BV22
Digital Output 3 Relay 2 Output OFF/ON R
BV23
Digital Output 4 Relay 3 Output OFF/ON R
BV24
Stop By Coast Indicates if drive stop by coast ON/OFF C
BV25
Stop By Ramp Indicates if drive stop by Ramp OFF/ON C
BV26
Belt Broken Indicates If belt is broken OFF/ON R
BV27
Drive Fan Failure Indicates if Drive Fan failed OFF/ON R
BV28
Force Bypass Command to take Drive in Bypass Mode OFF/ON C
BV29
Fire Mode Enable Fire Mode OFF/ON C
BV30
DIN 1 Fieldbus Digital Input OFF/ON C
BV31
DIN 2 Fieldbus Digital Input OFF/ON C
BV32
DIN 3 Fieldbus Digital Input OFF/ON C
BV33
DIN 4 Fieldbus Digital Input OFF/ON C
ote: N For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable.