87
PROFIBUS-DP External Communication Cards
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Table 104. Bypass mode process data modules
Module Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9
Module 1
CW REF FBData_In_1 FBData_In_2
SW ACT FBData_Out_1 FBData_Out_2
Module 2
CW REF FBData_In_1 FBData_In_2 FBData_In_3 FBData_In_4
SW ACT FBData_Out_1 FBData_Out_2 FBData_Out_3 FBData_Out_4
Module 3
CW REF FBData_In_1 FBData_In_2 FBData_In_3 FBData_In_4 FBData_In_5 FBData_In_6
SW ACT FBData_Out_1 FBData_Out_2 FBData_Out_3 FBData_Out_4 FBData_Out_5 FBData_Out_6
Module 4
CW REF FBData_In_1 FBData_In_2 FBData_In_3 FBData_In_4 FBData_In_5 FBData_In_6 FBData_In_7 FBData_In_8
SW ACT FBData_Out_1 FBData_Out_2 FBData_Out_3 FBData_Out_4 FBData_Out_5 FBData_Out_6 FBData_Out_7 FBData_Out_8
Only available in bypass mode.
Process data out
This register range is normally used to fast monitoring of
the VFD. Process Data Out is located in range ID 2104–2111.
See table below.
Table 105. Fieldbus basic output table
ID Modbus register Group Range/Type
2101 32101, 42101 FB Status Word Binary coded
2102 32102, 42102 FB General Status Word Binary coded
2103 32103, 42103 FB Actual Speed %
2104 32104, 42104 FB Process Data Out 1
2105 32105, 42105 FB Process Data Out 2
2106 32106, 42106 FB Process Data Out 3
2107 32107, 42107 FB Process Data Out 4
2108 32108, 42108 FB Process Data Out 5
2109 32109, 42109 FB Process Data Out 6
2110 32110, 42110 FB Process Data Out 7
2111 32111, 42111 FB Process Data Out 8
ote: N FB Process data is defined in Appendix B.
Status word
15141312111098 7 6 5 4 32 1 0
————————RUNENBYSAREFWARNFLTDIRRUNRDY
Information about the status of the device and messages is
indicated in the Status Word. The Status Word is composed
of 16 bits that have the following meanings.
Table 106. Status word bit descriptions
Bit
Description
value = 0 Value = 1
0Not Ready Ready
1STOP RUN
2 Clockwise Counterclockwise
3— Faulted
4— Warning
5 Ref. frequency not reached Ref. frequency reached
6 Bypass not activated Bypass activated
7 Run disable Run Enable
8 Not in use Not in use
9–15 Not in use Not In use
Actual speed
1514131211109876543210
MSB——————————————LSB
This is the Actual Speed of the motor.This value comes back
in the form of Hz.