84
PROFIBUS-DP External Communication Cards
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Table 102. PROFIBUS parameters
DG1/DH1
code Parameter Min. Max. Unit Default ID (Slot A/Slot B) Note
BX.1 Monitor
BX.1.1 Device Parameters
BX.1.1.1 Board Status 0 883/910 B0 = Optional Comm. Card Fault
B1 = Board HW Fault
B2 = Reserved
B3 = Fieldbus Fault
B4 = Reserved
BX.1.1.2 Firmware Version 10 64/1067 V1.06.0005
BX.1.1.3 Protocol Status 0 2131/2142 B0 = Waiting for Parameterization
B1 = Parameterization Fault
B2 = Waiting for Configuration
B3 = Configuration Fault
B4 = Data Exchange
BX.1.1.4 PDP-Telegram
Selection
1 1 1 1244/1252 1=Standard Telegram 1
BX.1.1.5 Fault Counter PDP 0 65535
BX.1.1.6 Fault Situations Max 8x8
BX.1.1.7 PDP-Profil Number 341
BX.1.1.8 PDP-Control Word 0x0000 0xFFFF
BX.1.1.9 PDP-Status Word 0x0000 0xFFFF
BX.1.2 Parameter Access
BX.1.2.1 PDP-
MaxBlockLength
30
BX.1.2.2 PDP-
NoOfMultiparameter
1
BX.1.2.3 PDP-MaxLatency 2
BX.1.3 DO Identification
BX.1.3.1 PDP-DO
Manufacturer
0x019D
BX.1.3.2 PDP-DO Device Type 0x3000
BX.1.3.3 PDP-DO
FW-Interface
BX.1.3.5 PDP-DO
FW-DayMonth
BX.1.3.6 PDP-DO NoOfDOs 1
BX.1.3.7 PDP-DO Subclass 1
BX.2 Parameters
BX.2.1 Slave Address 2 125 118 1242/1250 Address of the PROFIBUS Slave
BX.2.1 Baud Rate 1 10 10 1243/1251 Baud Rate for PROFIBUS
10 = Automatic
BX.2.2 Operation Mode 1 2 1 1245/1253 Operation Mode
0 = PROFIdrive
1 = Echo
2 = Bypass
BX.2.3 Comm. Card FB Fault
Response
2519/2520
BX.2.4 Parameter Access 0 1 1 0=Local Control;