199
Appendix A—Parameter ID list
POWERXL SERIES VFD MN040010EN—June 2018 www.eaton.com
Menu
Item
No.
Modbus
Register
PROFIBUS EtherNet/IP DeviceNet
Parameter
Description
Data
Type
Length
(in Bytes)
Display
FormatPNU
PNU
SubIndex Class Instance Attribute Class Instance Attribute
P21.4.76353223 16211718517Clear Trip MWh
Count
BOOLEAN 1 x0
P21.4.86368700 16211818518Trip Power Day CountINTEGER2x0
P21.4.9 637 871 0 162 1 19 185 1 9 Trip Power Hr Count DOUBLE 4 x0
P21.4.106393224 162120185110Clear Trip Power
Count
BOOLEAN 1 x0
B2.1.18837101 162115118611Board StatusBYTE1x0
B2.1.2 1064 NA NA 162 1 154 NA NA NA Firmware Version INTEGER 4 x0
B2.1.38897603 162116018612DI1, DI2, DI3 BYTE1x0
B2.1.4 888 761 3 162 1 159 186 1 3 DO1, DO2, DO3 BYTE 1 x0
B2.1.5891593100162116218614Thermistor ResistorDOUBLE4x0
B2.1.6887753100162115818615Thermistor StateBYTE1x0
B2.2.1241461100162115518616DO1 FunctionBYTE1x0
B2.2.2242461101162115618617DO2 FunctionBYTE1x0
B2.2.3243461102162115718618DO3 FunctionBYTE1x0
B2.2.4890343100162116118619Thermistor ConfigBOOLEAN1x0
B3.1.18837101 162115118611Board StatusBYTE1x0
B3.1.2 1064 NA NA 162 1 154 NA NA NA Firmware Version INTEGER 4 x0
B3.1.3 894 560 100 162 1 181 186 1 11 AI1 Value INTEGER 2 x1000
B3.1.4 897 570 100 162 1 184 186 1 12 AO1 Value INTEGER 2 x1000
B3.1.5 899 570 101 162 1 186 186 1 13 AO2 Value INTEGER 2 x1000
B3.2.1 893 263 100 162 1 180 186 1 14 AI1 Mode BYTE 1 x0
B3.2.2 124 260 100 162 1 164 186 1 15 AI1 Signal Range BYTE 1 x0
B3.2.3 125 264 100 162 1 165 186 1 16 AI1 Custom Min INTEGER 2 x100
B3.2.4 126 265 100 162 1 166 186 1 17 AI1 Custom Max INTEGER 2 x100
B3.2.5 123 266 100 162 1 179 186 1 18 AI1 Filter Time INTEGER 2 x100
B3.2.6 127 267 100 162 1 163 186 1 19 AI1 Signal Invert BOOLEAN 1 x0
B3.2.78962761001621183186120AO1 Mode BYTE1x0
B3.2.82354601001621167186121AO1 FunctionBYTE1x0
B3.2.9 238 279 100 162 1 168 186 1 22 AO1 Minimum BYTE 1 x0
B3.2.10 236 277 100 162 1 169 186 1 23 AO1 Filter Time INTEGER 2 x100
B3.2.112392741001621170186124AO1 Scale INTEGER2x0
B3.2.12 237 278 100 162 1 171 186 1 25 AO1 Inversion BOOLEAN 1 x0
B3.2.13 240 275 100 162 1 172 186 1 26 AO1 Offset INTEGER 2 x100
B3.2.14 898 276 101 162 1 185 186 1 27 AO2 Mode BYTE 1 x0
B3.2.152694601011621173186128AO2 FunctionBYTE1x0
B3.2.16 270 279 101 162 1 174 186 1 29 AO2 Minimum BYTE 1 x0
B3.2.17 271 277 101 162 1 175 186 1 30 AO2 Filter Time INTEGER 2 x100
B3.2.18 272 274 101 162 1 176 186 1 31 AO2 Scale INTEGER 2 x0
B3.2.19 273 278 101 162 1 177 186 1 32 AO2 Inversion BOOLEAN 1 x0
B3.2.20 274 275 101 162 1 178 186 1 33 AO2 Offset INTEGER 2 x100
B4.1.18837101 162115118611Board StatusBYTE1x0
B4.1.2 1064 NA NA 162 1 154 NA NA NA Firmware Version INTEGER 4 x0
B4.1.3 900 455 100 162 1 190 186 1 35 RO1, RO2, RO3 BYTE 1 x0
B4.2.15404511001621187186136RO1 FunctionBYTE1x0
B4.2.2 541 451 101 162 1 188 186 1 37 RO2 Function BYTE 1 x0
B4.2.3 551 451 102 162 1 189 186 1 38 RO3 Function BYTE 1 x0
B5.1.18837101 162115118611Board StatusBYTE1x0
B5.1.2 1064 NA NA 162 1 154 NA NA NA Firmware Version INTEGER 4 x0
B5.1.3 905 756 100 162 1 195 186 1 40 PT100 State INTEGER 6 x0
Table 205. DG1 Parameter ID list, continued