Integratethemeterwiththecontrolsystem
Procedure
SetDigitalCommunicationsFaultActionasdesired.
ThedefaultsettingisNone.
OptionsforDigitalCommunicationsFaultAction
OptionsforDigitalCommunicationsFaultActionareshowninT able7-15.
Table7-15OptionsforDigitalCommunicationsFaultAction
Code
ProLinkIIFieldCommunicatorDescription
UpscaleUpscale
Processvariablevaluesindicatethatthevalueis
greaterthantheuppersensorlimit.
T otalizersstopincrementing.
DownscaleDownscale
Processvariablevaluesindicatethatthevalueis
greaterthantheuppersensorlimit.
T otalizersstopincrementing.
ZeroIntZero-All0
Flowratevariablesgotothevaluethatrepresents
aowrateof0(zero).
Densityisreportedas0.
T emperatureisreportedas0°C,ortheequivalent
ifotherunitsareused(e.g.,32°F).
Drivegainisreportedasmeasured.
T otalizersstopincrementing.
Not-a-Number(NAN)
Not-a-Number
ProcessvariablesarereportedasIEEENAN.
Drivegainisreportedasmeasured.
ModbusscaledintegersarereportedasMaxInt.
T otalizersstopincrementing.
FlowtoZeroIntZero-Flow0
Flowratesarereportedas0.
Otherprocessvariablesarereportedasmeasured.
T otalizersstopincrementing.
None(default)None(default)
Allprocessvariablesarereportedasmeasured.
T otalizersincrementiftheyarerunning.
IfyousetmAOutputFaultActionorFrequencyOutputFaultActiontoNone,besuretosetDigital
CommunicationsFaultActiontoNone.Ifyoudonot,theoutputwillnotreportactualprocessdata,
andthismayresultinmeasurementerrororunintendedconsequencesforyourprocess.
IfyousetDigitalCommunicationsFaultActiontoNAN,youcannotsetmAOutputFaultActionor
FrequencyOutputFaultActiontoNone.Ifyoutrytodothis,thetransmitterwillnotacceptthe
conguration.