119
Reference Manual
00809-0100-2460, Rev DE
Service and Troubleshooting
October 2018
Service and Troubleshooting
7. Setup advanced filtering options for the ports to be logged. For each port you may choose:
a. any device address or a specific address
b. function code (Modbus), or TOR (Enraf
®
GPU)
c. status, i.e. various error type
8. Click the Apply button to start logging.
Logging will continue until it is stopped manually as described in “To stop logging” on page 120.
When the maximum number of files is reached, the first file will be overwritten. If no log filtering is
applied to a port, communication events for approximately 18-20 hours, equal to 100 MB of data
(maximum 10 files and 10 MB of data per file), will be available before being overwritten by newer
communication events.
It is recommended to turn off logging when it is not needed.
Debug Information
In case a status message such as “Warning Debug Info Exists” appears, you will have to press the Debug
Information Download button in order to clear this warning message. The download button lets you
store a data file that can be used for troubleshooting.
The Download button can be used even if no warning message appears. This allows you to use debug
information as a tool for advanced troubleshooting.