C.1 Tank Database configuration for Enraf devices
This section describes how to configure the Tank Database of the Rosemount
™
2460 System Hub for
supported Enraf devices. See also “Enraf
®
” on page 150 for information on hardware.
1. In TankMaster WinSetup right-click the Rosemount 2460 System Hub that the device is connected to
and choose Properties.
2. Select the Tank Database tab.
3. Find a free tank position (2460 Tank 1, 2, 3...) for the device to be configured.
Enraf device
Tank Database