171
Enraf
®
Device Configuration
Enraf
®
Device Configuration
October 2018
Reference Manual
00809-0100-2460, Rev DE
Appendix C Enraf
®
Device Configuration
Tank Database configuration for Enraf devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 171
Advanced Enraf configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 174
C.1 Tank Database configuration for Enraf devices
This section describes how to configure the Tank Database of the Rosemount
2460 System Hub for
supported Enraf devices. See also “Enraf
®
” on page 150 for information on hardware.
1. In TankMaster WinSetup right-click the Rosemount 2460 System Hub that the device is connected to
and choose Properties.
2. Select the Tank Database tab.
3. Find a free tank position (2460 Tank 1, 2, 3...) for the device to be configured.
Enraf device
Tank Database