October 2018
Reference Manual
00809-0100-2460, Rev DE
Table C-1. Summary of Tank Database entry fields
Entry field Description
Source Enraf
(1)
(811, 813, 854, 873, 894, 970, 971)
1. Enraf option is supported for 2460 firmware version 1.B0 and higher.
Field Port The field bus port that the selected device is connected to. Up to
six field ports may be used.
Level Device Address Enraf level device address. Each field device has its own unique
address in the range 00-99.
Temp Device Address Use the same address as the Enraf level device.
Number of Temp Elements “0” in case only average temperature is required. Otherwise the
total number of connected temperature elements.
In case you don’t need to monitor values for individual
temperature elements you should set this parameter to “0” in
order to avoid unnecessary load on the field bus.
Auxiliary Inputs
Free Water Level
Liquid Pressure
Middle Pressure
Vapor Pressure
Observed Density (UIn1)
Advanced
Vapor temperature
Fast polling