185
Whessoe Device Configuration
Whessoe Device Configuration
October 2018
Reference Manual
00809-0100-2460, Rev DE
3. Select the Advanced tab and click the Whessoe 550 button.
4. Enter the desired Low Range and High Range values for the appropriate pressure parameters.
The Advanced Whessoe 550 Configuration window lets you to set the Low Range and High Range values
for Vapor and Product pressure. These values allow the Rosemount 2460 to perform scaling of
collected pressure data to the correct values in bar.
The Use High Resolution Pressure option allows the system hub to increase resolution from the
standard 8 bit floating point value to a 13 bit resolution. However, this is not Whessoe standard and
may not be supported by the Whessoe device.
5. Click Apply to save the current configuration. Click OK to close the window.