192
Modbus
®
Standard Question
Modbus
®
Standard Question
October 2018
Reference Manual
00809-0100-2460, Rev DE
User Defined Register Area Priority 3 question
2560-2687 User Defined 1 Value FLOAT Unit is specified in Unit Register Area
below, see register 9344-9663.
Status is specified in Status Register
Area, see register 4224-4351.
2688-2815 User Defined 2 Value FLOAT
2816-2943 User Defined 3 Value FLOAT
2944-3071 User Defined 4 Value FLOAT
3072-3099 User Defined 5 Value FLOAT
Status Register Area
3968-4095 Standard Status DWORD Bitfield Priority 1 question
Bit 0: Simulated Level
Bit 1: Manual Level
Bit 2: Invalid Level
Bit 3: CFail Level
Bit 4: MI Approved Level
Bit 5: MI Legal Level
Bit 6: Backup Level used
Bit 7: Spare
Bit 8: Simulated FWL
Bit 9: Manual FWL
Bit 10: Invalid FWL
Bit 11: CFail FWL
Bit 12: Reserved
Bit 13: Reserved
Bit 14: Backup FWL used
Bit 15: Spare
Bit 16: Simulated Product Temp
Bit 17: Manual Product Temp
Bit 18: Invalid Product Temp
Bit 19: CFail Product Temp
Bit 20: MI Approved Product Temp
Bit 21: MI Legal Product Temp
Bit 22: Backup Product Temp used
Bit 23: Spare
Bit 24: Simulated Vapor Temp
Bit 25: Manual Vapor Temp
Bit 26: Invalid Vapor Temp
Bit 27: CFail Vapor Temp
Bit 28: MI Approved Vapor Temp
Bit 29: MI Legal Vapor Temp
Bit 30: Backup Vapor Temp used
Bit 31: Spare
Register
Number
Register Name Type Unit Description