194
Modbus
®
Standard Question
Modbus
®
Standard Question
October 2018
Reference Manual
00809-0100-2460, Rev DE
4224-4351 User Defined Value Status DWORD Bitfield Priority 3 question
Bit 0: Simulated User Def 1
Bit 1: Manual User Def 1
Bit 2: Invalid User Def 1
Bit 3: CFail User Def 1
Bit 4: Backup User Def 1 used
Bit 5: Spare
Bit 6: Simulated User Def 2
Bit 7: Manual User Def 2
Bit 8: Invalid User Def 2
Bit 9: CFail User Def 2
Bit 10: Backup User Def 2 used
Bit 11: Spare
Bit 12: Simulated User Def 3
Bit 13: Manual User Def 3
Bit 14: Invalid User Def 3
Bit 15: CFail User Def 3
Bit 16: Backup User Def 3 used
Bit 17: Spare
Bit 18: Simulated User Def 4
Bit 19: Manual User Def 4
Bit 20: Invalid User Def 4
Bit 21: CFail User Def 4
Bit 22: Backup User Def 4 used
Bit 23: Spare
Bit 24: Simulated User Def 5
Bit 25: Manual User Def 5
Bit 26: Invalid User Def 5
Bit 27: CFail User Def 5
Bit 28: Backup User Def 5 used
Bit 29: Spare
4352-4479 Temperature Element Status DWORD Bitfield Priority 3 question
Bit 0: Invalid value E1
..
Bit 15: Invalid value E16
Bit 16: Cfail E1
..
Bit 31: Cfail E16
4608-4671 Temperature Element in Product
Status
WORD Bitfield Bit 0: Element1 in product
..
Bit 15: Element16 in product
4672-4735 Temperature Element in Vapor
Status
WORD Bitfield Bit 0: E1 in vapor
..
Bit 15: E16 in vapor
4736-4799 Temperature Element Blocked
Status
WORD Bitfield Blocked from Avg. calculation
Bit 0: E1 is blocked.
..
Bit 15: E16 is blocked
Register
Number
Register Name Type Unit Description

Table of Contents

Related product manuals