Technical data Proline t-mass I 300 HART
170 Endress+Hauser
Damping Configurable: 0 to 999.9 s
Assignable measured
variables
Mass flow
Volume flow
Corrected volume flow
FAD volume flow
Flow velocity
Temperature
Energy flow
Pressure
Density
Heat flow
Electronics temperature
2nd temperature heat difference
For SIL (application package), only mass flow
Current output 4 to 20 mA
Order code "Output; input 2" (21), "Output; input 3" (022):
Option B: current output 4 to 20 mA
Signal mode Can be set to:
Active
Passive
Current span Can be set to:
4 to 20 mA NAMUR
4 to 20 mA US
4 to 20 mA
0 to 20 mA (only if the signal mode is active)
Fixed current
Maximum output values 22.5 mA
Open-circuit voltage DC 28.8 V (active)
Maximum input voltage DC 30 V (passive)
Load 0 to 700 Ω
Resolution 0.38 µA
Damping Configurable: 0 to 999.9 s
Assignable measured
variables
Mass flow
Volume flow
Corrected volume flow
FAD volume flow
Flow velocity
Temperature
Energy flow
Pressure
Density
Heat flow
Electronics temperature
2nd temperature heat difference
For SIL (application package), only mass flow
Pulse/frequency/switch output
Function Can be set to pulse, frequency or switch output
Version Open collector
Can be set to:
Active
Passive
Passive NAMUR
Maximum input values DC 30 V, 250 mA (passive)