Commissioning Proline t-mass I 300 HART
90 Endress+Hauser
0/4 mA value
→ 91
20 mA value
→ 91
Fixed current
→ 91
Terminal number
→ 90
Damping output 1 to n
→ 91
Failure mode
→ 91
Terminal number
→ 90
Failure current
→ 91
Terminal number
→ 90
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Assign current output 1 to n – Select process variable for
current output.
• Off
*
• Temperature
• Mass flow
• Corrected volume
flow
• FAD volume flow
*
• Volume flow
• Energy flow
*
• Heat flow
*
• Density
• Flow velocity
• Pressure
• 2nd temperature
delta heat
*
• Electronic
temperature
–
Terminal number – Shows the terminal numbers
used by the current output
module.
• Not used
• 26-27 (I/O 1)
• 24-25 (I/O 2)
• 22-23 (I/O 3)
–
Current span – Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
• 4...20 mA (4...
20.5 mA)
• 0...20 mA (0...
20.5 mA)
• Fixed current
Country-specific:
• 4...20 mA NAMUR
(3.8...20.5 mA)
• 4...20 mA US
(3.9...20.8 mA)
Signal mode – Select the signal mode for the
current output.
• Active
*
• Passive
*
Active