Proline t-mass I 300 HART Commissioning
Endress+Hauser 97
Parameter Prerequisite Description Selection / User
interface / User
entry
Factory setting
Switch output function The Switch option is selected
in the Operating mode
parameter parameter.
Select function for switch
output.
• Off
• On
• Diagnostic
behavior
• Limit
• Flow direction
check
*
• Status
–
Assign diagnostic behavior • In the Operating mode
parameter, the Switch
option is selected.
• In the Switch output
function parameter, the
Diagnostic behavior option
is selected.
Select diagnostic behavior for
switch output.
• Alarm
• Alarm or warning
• Warning
–
Assign limit • The Switch option is
selected in the Operating
mode parameter.
• The Limit option is selected
in the Switch output
function parameter.
Select process variable for limit
function.
• Temperature
• Mass flow
• Corrected volume
flow
• FAD volume flow
*
• Volume flow
• Energy flow
*
• Heat flow
*
• Density
• Flow velocity
• 2nd temperature
delta heat
*
• Electronic
temperature
• Totalizer 1
• Totalizer 2
• Totalizer 3
–
Assign status • The Switch option is
selected in the Operating
mode parameter.
• The Status option is
selected in the Switch
output function parameter.
Select device status for switch
output.
• Off
• Low flow cut off
–
Switch-on value • The Switch option is
selected in the Operating
mode parameter.
• The Limit option is selected
in the Switch output
function parameter.
Enter measured value for the
switch-on point.
Signed floating-point
number
Depends on country
and nominal
diameter
Switch-off value • The Switch option is
selected in the Operating
mode parameter.
• The Limit option is selected
in the Switch output
function parameter.
Enter measured value for the
switch-off point.
Signed floating-point
number
–
Switch-on delay • The Switch option is
selected in the Operating
mode parameter.
• The Limit option is selected
in the Switch output
function parameter.
Define delay for the switch-on
of status output.
0.0 to 100.0 s –