Levelflex FMP55 HART Operating menu
Endress+Hauser 129
Selection SI units
mm
m
US units
ft
in
Factory setting m
Tank type
Navigation  Setup → Tank type
Prerequisite Medium type = Liquid
Description Select tank type.
Selection Metallic
Bypass / pipe
Non metallic
Mounted outside
Coaxial
Factory setting Depending on the probe
Additional information Depending on the probe some of the options mentioned above may not be available or
there may be additional options.
For coax probes and probes with metallic center washer Tank type parameter
corresponds to the type of probe and cannot be changed.
Tube diameter
Navigation  Setup → Tube diameter
Prerequisite Tank type (→  129) = Bypass / pipe
The probe is coated.
Description Specify diameter of bypass or stilling well.
User entry 0 to 9.999 m
Factory setting 0.0384 m
Medium group
Navigation  Setup → Medium group
Prerequisite For FMP51/FMP52/FMP54/FMP55: Operating mode (→  128) = Level
Medium type = Liquid