Operating menu Levelflex FMP55 HART
154 Endress+Hauser
Interface linearized
Navigation Setup → Advanced setup → Linearization → Interface linearized
Prerequisite Operating mode (→ 128) = Interface or Interface with capacitance
Description Displays the linearized interface height.
Additional information The unit is defined in the Unit after linearization parameter → 152.
Maximum value
Navigation Setup → Advanced setup → Linearization → Maximum value
Prerequisite Linearization type (→ 151) has one of the following values:
• Linear
• Pyramid bottom
• Conical bottom
• Angled bottom
• Horizontal cylinder
• Sphere
Description Linearized value corresponding to a level of 100%.
User entry –50 000.0 to 50 000.0 %
Factory setting 100.0 %
Diameter
Navigation Setup → Advanced setup → Linearization → Diameter
Prerequisite Linearization type (→ 151) has one of the following values:
• Horizontal cylinder
• Sphere
Description Diameter of the cylindrical or spherical tank.
User entry 0 to 9 999.999 m
Factory setting 2 m
Additional information The unit is defined in the Distance unit parameter (→ 128).