EasyManua.ls Logo

Endress+Hauser Levelflex FMP55 - Power Supply

Endress+Hauser Levelflex FMP55
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical connection Levelflex FMP55 HART
46 Endress+Hauser
7.1.4 Power supply
2-wire, 4-20mA HART, passive
2-wire; 4-20mA HART
1)
"Approval"
2)
Terminal voltage U at the device Maximum load R, depending on the supply voltage U
0
at the
supply unit
Non-Ex
Ex nA
Ex ic
CSA GP
17.5 to 35 V
3)
R
U
0
[V]
10
17.5
28.5
20 30 35
0
500
[ ]W
A0014079
Ex ia / IS 17.5 to 30 V
3)
Ex d / XP
Ex ic[ia]
Ex tD / DIP
16 to 30 V
3)
R [ ]Ω
U
0
[V]
10
16 27
20 30
0
500
A0034970
1) Feature 020 of the product structure: option A
2) Feature 010 of the product structure
3) If the Bluetooth modem is used, the minimum supply voltage increases by 2 V.
2-wire; 4-20 mA HART, switch output
1)
"Approval"
2)
Terminal voltage U at the device Maximum load R, depending on the supply voltage U
0
at the
supply unit
Non-Ex
Ex nA
Ex nA[ia]
Ex ic
Ex ic[ia]
Ex d[ia] / XP
Ex ta / DIP
CSA GP
16 to 35 V
3)
U
0
[V]
10
16 27
20 30 35
0
500
R [ ]Ω
A0034972
Ex ia / IS
Ex ia + Ex d[ia] / IS + XP
16 to 30 V
3)
1) Feature 020 of the product structure: option B
2) Feature 010 of the product structure
3) If the Bluetooth modem is used, the minimum supply voltage increases by 2 V.