Electrical connection Levelflex FMP55 HART
50 Endress+Hauser
5. Connect the cable in accordance with the terminal assignment.
2
1
4
3
2
1
4
3
A0034682
6. If using shielded cables: Connect the cable shield to the ground terminal.
7.2.3 Plug-in spring-force terminals
In the case of devices without integrated overvoltage protection, electrical connection is via
plug-in spring-force terminals. Rigid conductors or flexible conductors with ferrules can be
inserted directly into the terminal without using the lever, and create a contact
automatically.
3 (0.12)
1. 2.
A0013661
 22 Dimensions: mm (in)
To remove cables from the terminal:
1. Using a flat-blade screwdriver ≤ 3 mm, press down on the slot between the two
terminal holes
2. while simultaneously pulling the cable end out of the terminal.
7.2.4 Closing connection compartment cover
1.
2.
2,5 Nm
3 mm
A0021491