Levelflex FMP55 HART Operating menu
Endress+Hauser 159
"Safety settings" submenu
Navigation  Setup → Advanced setup → Safety settings
Output echo lost
Navigation  Setup → Advanced setup → Safety settings → Output echo lost
Description Output signal in case of a lost echo.
Selection Last valid value
Ramp at echo lost
Value echo lost
Alarm
Factory setting Last valid value
Additional information Meaning of the options
Last valid value
The last valid value is kept in the case of a lost echo.
Ramp at echo lost
9)
In the case of a lost echo the output value is continously shifted towards 0% or 100%.
The slope of the ramp is defined in the Ramp at echo lost parameter (→  160).
Value echo lost
9)
In the case of a lost echo the output assumes the value defined in the Value echo lost
parameter (→  159).
Alarm
In the case of a lost echo the device generates an alarm; see the Failure mode parameter
(→  169)
Value echo lost
Navigation  Setup → Advanced setup → Safety settings → Value echo lost
Prerequisite Output echo lost (→  159) = Value echo lost
Description Output value in case of a lost echo
User entry 0 to 200 000.0 %
Factory setting 0.0 %
Additional information Use the unit which has been defined for the measured value output:
without linearization: Level unit (→  143)
with linearization: Unit after linearization (→  152)