Levelflex FMP55 HART Operating menu
Endress+Hauser 175
Switch-off delay
Navigation  Setup → Advanced setup → Switch output → Switch-off delay
Prerequisite Switch output function (→  171) = Limit
Assign limit (→  172)Off
Description Defines the delay applied before the output is switched off.
User entry 0.0 to 100.0 s
Factory setting 0.0 s
Failure mode
Navigation  Setup → Advanced setup → Switch output → Failure mode
Prerequisite Switch output function (→  171) = Limit or Digital Output
Description Defines the state of the switch output in case of an error.
Selection Actual status
Open
Closed
Factory setting Open
Additional information
Switch status
Navigation  Setup → Advanced setup → Switch output → Switch status
Description Current status of the switch output.
Invert output signal
Navigation  Setup → Advanced setup → Switch output → Invert output signal
Description 'No' The switch output behaves as per its parameter setting. 'Yes' The switching behavior is
inverted as compared to its parameter setting.
Selection No
Yes