Levelflex FMP55 HART Operating menu
Endress+Hauser 205
Factory setting Off
Additional information An active simulation is indicated by a diagnostic message of the Function check (C)
category.
Value current output 1 to 2
Navigation  Expert → Diagnostics → Simulation → Value current output 1 to 2
Prerequisite Current output simulation (→  204) = On
Description Defines the value of the simulated output current.
User entry 3.59 to 22.5 mA
Factory setting 3.59 mA
Additional information The current output assumes the value specified in this parameter. In this way, users can
verify the correct adjustment of the current output and the correct function of connected
control units.
Switch output simulation
Navigation  Expert → Diagnostics → Simulation → Switch output simulation
Description Switch the simulation of the switch output on and off.
Selection Off
On
Factory setting Off
Switch status
Navigation  Expert → Diagnostics → Simulation → Switch status
Prerequisite Switch output simulation (→  205) = On
Description Current status of the switch output.
Selection Open
Closed
Factory setting Open