Levelflex FMP55 HART Commissioning via operating menu
Endress+Hauser 83
12.7 Configuration management
After commissioning, you can save the current device configuration, copy it to another
measuring point or restore the previous device configuration. You can do so using the
Configuration management parameter and its options.
Navigation path in the operating menu
Setup → Advanced setup → Configuration backup display → Configuration management
Meaning of the options
Cancel
No action is executed and the user exits the parameter.
Execute backup
A backup copy of the current device configuration in the HistoROM (built-in in the
device) is saved to the display module of the device. The backup copy comprises the
transmitter and sensor data of the device.
Restore
The last backup copy of the device configuration is copied from the display module to the
HistoROM of the device. The backup copy comprises the transmitter and sensor data of
the device.
Duplicate
The transmitter configuration is duplicated to another device using the transmitter
display module. The following parameters, which characterize the individual measuring
point are not included in the transmitted configuration:
HART date code
HART short tag
HART message
HART descriptor
HART address
Device tag
Medium type
Compare
The device configuration saved in the display module is compared to the current device
configuration of the HistoROM. The result of this comparison is displayed in the
Comparison result parameter.
Clear backup data
The backup copy of the device configuration is deleted from the display module of the
device.
While this action is in progress, the configuration cannot be edited via the local
display and a message on the processing status appears on the display.
If an existing backup is restored to a different device using the Restore option, it may
occur that some device functionalities are no longer available. In some cases even a
device reset →  186 will not restore the original status..
In order to transmit a configuration to a different device, the Duplicate option should
always be used.