Operating menu Levelflex FMP55 HART
172 Endress+Hauser
Assign status
Navigation Setup → Advanced setup → Switch output → Assign status
Prerequisite Switch output function (→ 171) = Digital Output
Selection • Off
• Digital output AD 1
• Digital output AD 2
Factory setting Off
Additional information The Digital output AD 1 and Digital output AD 2 options refer to the Advanced
Diagnostic Blocks. A switch signal generated in these blocks can be transmitted via the
switch output.
Assign limit
Navigation Setup → Advanced setup → Switch output → Assign limit
Prerequisite Switch output function (→ 171) = Limit
Selection • Off
• Level linearized
• Distance
• Interface linearized
*
• Interface distance
*
• Thickness upper layer
*
• Terminal voltage
• Electronic temperature
• Measured capacitance
*
• Relative echo amplitude
• Relative interface amplitude
*
• Absolute echo amplitude
• Absolute interface amplitude
*
Factory setting Off
Assign diagnostic behavior
Navigation Setup → Advanced setup → Switch output → Assign diagnostic behavior
Prerequisite Switch output function (→ 171) = Diagnostic behavior
Description Defines to which behavior of diagnostic events the switch output reacts.