Operation options Levelflex FMP55 HART
56 Endress+Hauser
8.2 Structure and function of the operating menu
8.2.1 Structure of the operating menu
Menu Submenu /
parameter
Meaning
Language
1)
Defines the operating language of the on-
site display
Commissioning
2)
Launches the interactive wizard for guided
commissioning.
Additional settings generally do not need
to be made in the other menus when the
wizard is finished.
Setup Parameter 1
...
Parameter N
Once values have been set for these
parameters, the measurement should
generally be completely configured.
Advanced setup Contains additional submenus and
parameters:
to adapt the device to special measuring
conditions.
to process the measured value (scaling,
linearization).
to configure the signal output.
Diagnostics Diagnostic list Contains up to 5 currently active error
messages.
Event logbook
3)
Contains the last 20 messages (which are
no longer active).
Device information Contains information for identifying the
device.
Measured values Contains all current measured values.
Data logging Contains the history of the individual
measuring values.
Simulation Is used to simulate measured values or
output values.
Device check Contains all parameters needed to check
the measurement capability of the device.
Heartbeat
4)
Contains all the wizards for the Heartbeat
Verification and Heartbeat Monitoring
application packages.
Expert
5)
Contains all parameters of the device
(including those that are already in one of
the other menus). This menu is organized
according to the function blocks of the
device.
The parameters of the Expert menu are
described in:
GP01000F (HART)
System Contains all higher-order device
parameters that do not concern the
measurement or measured value
communication.
Sensor Contains all parameters needed to
configure the measurement.
Output Contains all parameters needed to
configure the current output.
Contains all parameters needed to
configure the switch output (PFS).