EasyManua.ls Logo

Endress+Hauser Levelflex FMP55 - Failure Current; Output Current 1 to 2

Endress+Hauser Levelflex FMP55
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating menu Levelflex FMP55 HART
170 Endress+Hauser
Additional information Meaning of the options
Min.
The current output adopts the value of the lower alarm level according to the Current
span parameter (→  168).
Max.
The current output adopts the value of the upper alarm level according to the Current
span parameter (→  168).
Last valid value
The current remains constant at the last value it hat before the error occurred.
Actual value
The output current follows the actual measured value; the error is ignored.
Defined value
The output current assumes the value defined in the Failure current parameter
(→  170).
The error behavior of other output channels is not influenced by these settings but is
defined in separate parameters.
Failure current
Navigation  Setup → Advanced setup → Current output 1 to 2 → Failure current
Prerequisite Failure mode (→  169) = Defined value
Description Defines which current the output assumes in case of an error.
User entry 3.59 to 22.5 mA
Factory setting 22.5 mA
Output current 1 to 2
Navigation  Setup → Advanced setup → Current output 1 to 2 → Output current 1 to 2
Description Shows the actual calculated value of the output current.

Table of Contents

Other manuals for Endress+Hauser Levelflex FMP55

Related product manuals