Levelflex FMP55 HART Operating menu
Endress+Hauser 133
Signal quality
Navigation  Setup → Signal quality
Description Displays the signal quality of the evaluated echo.
Additional information Meaning of the display options
Strong
The evaluated echo exceeds the threshold by at least 10 mV.
Medium
The evaluated echo exceeds the threshold by at least 5 mV.
Weak
The evaluated echo exceeds the threshold by less than 5 mV.
No signal
The device does not find a usable echo.
The signal quality indicated in this parameter always refers to the currently evaluated
echo: either the level/interface echo
5)
or the end-of-probe echo. To differentiate between
these two, the quality of the end-of-probe echo is always displayed in brackets.
In case of a lost echo (Signal quality = No signal) the device generates the following
error message:
F941, for Output echo lost (→  159) = Alarm.
S941, if another option has been selected in Output echo lost (→  159).
DC value
Navigation  Setup → DC value
Prerequisite The device has the "interface measurement" application package
6)
.
Description Specify relative dielectric constant ε
r
of the upper medium (DC
1
).
User entry 1.0 to 100
Factory setting 2.0
5) Of these two echos the one with the lower quality is indicated.
6) Product structure: Feature 540 "Application Package", Option EB "Interface measurement"