Levelflex FMP55 HART Operating menu
Endress+Hauser 141
"Interface" submenu
Navigation  Setup → Advanced setup → Interface
Process property
Navigation  Setup → Advanced setup → Interface → Process property
Description Specify typical rate of change for the interface position.
Selection Fast > 1 m (40 in)/min
Standard < 1 m (40in) /min
Medium < 10 cm (4in) /min
Slow < 1 cm (0.4in) /min
No filter / test
Factory setting Standard < 1 m (40in) /min
Additional information The device adjusts the signal evaluation filters and the damping of the output signal to the
typical rate of level change defined in this parameter:
Process property Step response time / s
Fast > 1 m (40 in)/min 5
Standard < 1 m (40in) /min 15
Medium < 10 cm (4in) /min 40
Slow < 1 cm (0.4in) /min 74
No filter / test 2.2
Interface property
Navigation  Setup → Advanced setup → Interface → Interface property
Prerequisite Operating mode (→  128) = Interface with capacitance
Description Select interface property.
The interface property determines how the Guided Radar and the Capacitance
Measurement interact.
Selection Special: automatic DC
Build up
Standard
Emulsion layer
Factory setting Standard