Levelflex FMP55 HART Operating menu
Endress+Hauser 171
"Switch output" submenu
The Switch output submenu (→  171) is only visible for devices with switch
output.
13)
Navigation  Setup → Advanced setup → Switch output
Switch output function
Navigation  Setup → Advanced setup → Switch output → Switch output function
Description Defines the function of the switch output. 'Off' The switch output is always open (non-
conductive) 'On' The switch output is always closed (conductive). 'Diagnostic behavior' The
switch output is normally closed and is only opened if a diagnostic event is present. 'Limit'
The switch output is normally closed and is only opened if a measured variable exceeds a
defined limit. 'Digital output' The switch output is controlled by one of the digital output
blocks of the device.
Selection Off
On
Diagnostic behavior
Limit
Digital Output
Factory setting Off
Additional information Meaning of the options
Off
The output is always open (non-conductive).
On
The output is always closed (conductive).
Diagnostic behavior
The output is normally closed and is only opened if a diagnostic event is present. The
Assign diagnostic behavior parameter (→  172) determines for which type of event
the output is opened.
Limit
The output is normally closed and is only opened if a measured variable exceeds or falls
below a defined limit. The limit values are defined by the following parameters:
Assign limit (→  172)
Switch-on value (→  173)
Switch-off value (→  174)
Digital Output
The switching state of the output tracks the output value of a DI function block. The
function block is selected in the Assign status parameter (→  172).
The Off and On options can be used to simulate the switch output.