Operating menu Levelflex FMP55 HART
204 Endress+Hauser
Description of parameters
Navigation  Expert → Diagnostics → Simulation
Assign measurement variable
Navigation  Expert → Diagnostics → Simulation → Assign measurement variable
Selection Off
Level
Interface
*
Thickness upper layer
*
Level linearized
Interface linearized
Thickness linearized
Factory setting Off
Additional information The value of the variable to be simulated is defined in the Process variable value
parameter (→  204).
If Assign measurement variableOff, a simulation is active. This is indicated by a
diagnotic message of the Function check (C) category.
Process variable value
Navigation  Expert → Diagnostics → Simulation → Process variable value
Prerequisite Assign measurement variable (→  204)Off
User entry Signed floating-point number
Factory setting 0
Additional information Downstream measured value processing and the signal output use this simulation value. In
this way, users can verify whether the measuring device has been configured correctly.
Current output 1 to 2 simulation
Navigation  Expert → Diagnostics → Simulation → Current output 1 to 2 simulation
Description Switch the simulation of the current output on and off.
Selection Off
On
* Visibility depends on order options or device settings