Operating menu Levelflex FMP55 HART
208 Endress+Hauser
Level signal
Navigation  Diagnostics → Device check → Level signal
Prerequisite Device check has been performed.
Description Displays result of the device check for the level signal.
User interface Check not done
Check not OK
Check OK
Additional information For Level signal = Check not OK: Check the mounting position of the device and the
dielectric constant of the medium.
Launch signal
Navigation  Diagnostics → Device check → Launch signal
Prerequisite Device check has been performed.
Description Displays result of the display check for the launch signal.
User interface Check not done
Check not OK
Check OK
Additional information For Launch signal = Check not OK: Check the mounting position of the device. In non-
metallic vessels use a metal plate or a metal flange.
Interface signal
Navigation  Diagnostics → Device check → Interface signal
Prerequisite Operating mode (→  128) = Interface or Interface with capacitance
Device check has been performed.
Description Displays result of the device check for the interface signal.
User interface Check not done
Check not OK
Check OK