Mounting Levelflex FMP55 HART
32 Endress+Hauser
L
CAUTION
The plugs of the connection cable may be damaged by mechanical stress.
Mount the probe and the electronics housing tightly before connecting the cable.
Lay the cable such that it is not exposed to mechanical stress. Minimum bending
radius: 100 mm (4").
When connecting the cable: Connect the straight plug before the angled one. Torque
for both coupling nuts: 6 Nm.
Probe, electronics and connection cable are adjusted to match each other. They are
marked by a common serial number. Only components with the same serial number
shall be connected to each other.
If the measuring point is exposed to strong vibrations, an additional locking
compound (e.g. Loctite 243) can be applied at the plug connectors.
Mounting the electronics housing
122 (4.8)
52 (2)
86
(3.4)
70
(2.8)
127...140
(5...5.51)
161 (6.34)
162...175
(6.38...6.89)
A B
ø42...60
(1.65...2.36)
A0014793
 6 Mounting the electronics housing using the mounting bracket; dimensions: mm (in)
A Wall mounting
B Pipe mounting
Connecting the cable
Required tools:
Open-end wrench 18AF