Parameter overview with brief description
Parameter Description Selection / User entry / User
interface
Factory setting
Electrodeйcleaningйcircuit Enableйtheйcyclicйelectrodeйcleaningйcircuit. • Off
• On
Off
ECCйduration Enterйtheйdurationйofйelectrodeйcleaningйin
seconds.
0.01йtoй30йs 2йs
ECCйrecoveryйtime Defineйrecoveryйtimeйafterйelectrode
cleaning.йDuringйthisйtimeйtheйcurrentйoutput
valuesйwillйbeйheldйatйlastйvalidйvalue.
1йtoй3.0
+38
йs 60йs
ECCйcleaningйcycle Enterйtheйpauseйdurationйbetweenйelectrode
cleaningйcycles.
0.5йtoй168йh 0.5йh
ECCйPolarity Selectйtheйpolarityйofйtheйelectrodeйcleaning
circuit.
• Positive
• Negative
Positive
10.5 Simulation
Theй"Simulation" submenuйenablesйyouйtoйsimulate,йwithoutйaйrealйflowйsituation,йvarious
processйvariablesйinйtheйprocessйandйtheйdeviceйalarmйmodeйandйtoйverifyйdownstream
signalйchainsйсswitchingйvalvesйorйclosed-controlйloops).
Navigation
"Diagnostics"йmenuййSimulation
Simulation
Assignйsimulationйprocessйvariable
Valueйprocessйvariable
Simulationйdeviceйalarm
Simulationйdiagnosticйevent
Parameter overview with brief description
Parameter Prerequsite Description Selection / User
entry
Factory setting
Assignйsimulationйprocessйvariable – Selectйaйprocessйvariableйfor
theйsimulationйprocessйthatйis
activated.
• Off
• Volumeйflow
• Massйflow
• Correctedйvolume
flow
• Conductivity
• Corrected
conductivity
• Temperature
Off
Valueйprocessйvariable Aйprocessйvariableйisйselected
inйtheйAssign simulation
process variableйparameter.
Enterйtheйsimulationйvalueйfor
theйselectedйprocessйvariable.
Signedйfloating-point
number
0